H.A. Jones, OBE, MIE Aust.

H.A. Jones is well qualified to write the history of electricity supply in the ACT. He joined the Federal Capital Commission in 1928 as a Cadet and was actively associated with all phases of electricity supply in Canberra from those early years right through to his retirement in 1975: even when away he kept in touch.

After a break in 1943 to carry out wartime defence work, he returned to the Department of Works, Canberra, in 1949 as senior electrical engineer, and on the retirement of Mr W.E. Gray, became supervising electrical engineer. In 1953 he was appointed engineer manager, Canberra Electricity Supply, Department of the Interior, and with formation of the ACT Electricity Authority in 1963 he became its first Chairman, a position he held until retirement.

THE first permanent building in the National Capital was the power station at Kingston. It was designed by the Department of Home Affairs in 1912 and completed in time to generate electricity in August 1915. The new building was the realisation of the dream of the Capital’s founders that the city should be all-electric, which was a far-sighted view early in this century when electricity had only recently been made available in Sydney and Melbourne on a restricted basis.

The Seat of Government Acceptance Act 1909 had made provision for the supply of electricity to the Capital by hydro-electric power utilising the abundant waters of the Snowy Mountains in New South Wales. The Act stated:

'The State shall grant to the Commonwealth without payment therefor the right to use the waters of the Snowy River and other such rivers as may be agreed upon or in default of agreement may be determined by arbitration for the generation of electricity for the purposes of the Territory and to construct the works necessary for that purpose and to conduct the electricity so generated to the Territory.'

Development of a Snowy River hydro-electric scheme did not begin until 1949 but in 1911 steam power generation was seen as the means of supplying electricity to the new Capital. On 10 July of that year, Mr F.W. Clements M. Inst. CE MIEE, Chief Engineer and General Manager, Melbourne Electric Supply Co., submitted a report to Colonel P.T. Owen, Director General of Works, Public Works Branch, Department of Home Affairs on ‘A General Electric Supply Scheme for the Proposed Federal Capital at Canberra’. In this report Mr Clements outlined a scheme which would be suitable for:

  1. Electrical requirements during construction of the Capital,
  2. the permanent general electric supply,
  3. Supply Pumping Station at the Cotter River. the provision of power for the proposed Water

A steam power station was specified and the recommendations of his report were followed. His basic recommendation to use alternating current three phase four wire fifty cycles with a generating voltage of 5,000-5,500 volts was far sighted in those days, especially as he was asked to recommend an electric supply for a City of 25,000 inhabitants and having regard to the development of electric supply at that date.

Power Station building
Fig. 6.1: Power Station building at Kingston, 1915.
cooling water at Power Station
Fig. 6.2: Weir for cooling water at Power Station near the present Kings Avenue Bridge. Footbridge removed and concrete roadway added later. Photo: A.E. Minty 1959.
Rear of Power Station
Fig. 6.3: Rear of Power Station building Kingston showing economiser room and original stack 1915.

It was decided to build a power station at Interlake Avenue (Wentworth Avenue, Kingston) adjacent to the Molonglo River where a small dam was built to provide a source of cooling water for the condensers of the steam generating sets. The building, designed and constructed by the Department of Home Affairs, was commenced in 1912 and started generating electricity in August, 1915. The building allowed for the generating equipment recommended by Mr F.W. Clements with assistance on the steam side from Mr Christie, a Consulting Marine Engineer from Sydney.

The power station was not built on the site nominated by Griffin in his prize winning plan but on a site selected according to the Departmental Board’s plan which was substituted for Griffin’s and to which construction of the City was then committed. Griffin had shown the power station to be on the northern shore of his East Basin, below Russell Hill. Subsequently, at the 1916 Royal Commission of Inquiry, Griffin did not object to the location chosen by the Board on the southern shore of the Molonglo River.

The Department decided to build a solid steel and concrete building with brick curtain walls. One and a half million bricks were made and put to grass but unfortunately they were made by the dry press process unsuitable for Canberra’s shale and they disintegrated. The curtain walls were then made of unreinforced concrete made with river gravel.

The power station at the time was considered to be the most modern in Australia, but progress soon made it old fashioned. However, it had some eminence in the early days as a permanent land mark, and late at night its lights served as a beacon to guide many Canberra folk home from Queanbeyan late at night.

When a group of houses was built in a suburb most of the roads were constructed and temporary street lighting was installed along the footpaths included in the road reservation. These were open street lights on wooden poles about 95 metres apart and were to be replaced when the street trees grew. After viewing these illuminations from Red Hill one night a visitor remarked to the Secretary of the Prime Minister’s Department that it was a wonderful sight. “Yes. Paris at night and Arabia in the morning”, answered the bureaucrat. Press Gallery journalists who didn’t like Canberra, called it ‘the only illuminated cemetery in the world!’

The few early residents in houses had electricity provided at a reasonable flat rate of 7s.6d. per month from about 1916 to 1922 when metering was installed and a tariff struck.

The train from Queanbeyan stopped outside the power station until the railway station was built, and the power station even made ice packed in sawdust which was delivered by horse and dray to the Bachelor’s Quarters and houses at Acton.

The total cost of the power station was 76,861 which included 37,501 for the plant, a large expenditure in those days.

The first installation of generating equipment in the power station comprised:

Two Bellis and Morcom triple expansion engines running at 250 rpm and exhausting into condensers but each fitted with flanges to render them suitable later to exhaust into an exhaust turbine. These were direct coupled to Brush Alternators of 600 kW capacity at 0.8 power factor lagging and generating 5,000/5,500 volts, three phase 50 cycles.

One Robey-Hall twin cylinder steam engine direct coupled to a 150kW alternator was installed to be used at periods of very light load.

Bellis and Morcom engines
Fig. 6.4: Bellis and Morcom engines just erected in 1915 with W. Brown, later foreman linesman for many years.
Photo: Bert Brown.

The Boiler Plant comprised four double drum Babcock and Wilcox boilers with chain grate under fired stokers and with superheaters. Each boiler would evaporate 15,000 lb of water per hour at a pressure of 180 lb per square inch superheated to 550 F.

Induced draft fans were provided and a Greens Economiser raised the feed water temperature from 140 to 260 F.

It is worth noting that the original 5,500 volt main switchboard installed in 1915, despite the fact that it was outmoded and could not handle the available fault current, remained in service for about forty years by necessity. Switchgear fires were not unknown but they were extinguished and it carried on until it could be replaced.

Canberra’s first supply of public electricity generated at the Eastlake (Kingston) Steam Power Station from August 1915, was conveyed to Duntroon and Acton on 5,500 volt overhead lines and in 1916 to the Brickworks at 5,500 volts and to the Cotter Pumping Station at 11,000 volts. The first Brickworks motors were run from 11 October, 1916, and the first Cotter Pumping on 16 October, 1918.

A large length of power line for construction mainly of the main sewers was also installed.

The general 5,500 volt overhead lines were mounted on very large swan neck pins with American “Locke” 6,000 volt insulators and with an overhead earth wire. In the middle thirties, this construction was changed to three feet equilateral spacing with a pole top bracket and Australian insulators. The above types of construction were adopted to reduce tree interference because of the narrow clearance required.

On 22 October, 1927 a BTH Curtis type turbo-alternator was connected to the main steam range. This ran at 3,000 rpm and generated 1,500 kW at 0.8 lagging power factor, at 5,500 volts 50 cycles. At this time the Robey-Hall machine was discarded.

Although the addition of this turbine enabled electricity to be produced more economically and in fact the retail tariff was reduced, the Southern Electric Supply Branch of the NSW Department of Public Works submitted a proposition to the Federal Capital Commission to provide electricity from Burrinjuck at an even cheaper rate. This was accepted and some 80 miles of 66 kV three phase line was constructed by the Southern Electric Supply from Burrinjuck Hydro-Electric Station to Canberra.

At the irrigation dam at Burrinjuck Lake the Public Works Department of New South Wales had installed two 5,000 kW hydro-electric alternators for which, without Canberra, they had insufficient loading in the south of New South Wales. Canberra’s supply was taken from Burrinjuck from 1929 to 1938 on a single radial line nearly 80 miles long with the local steam plant remaining as standby.

In the middle thirties, doubt arose regarding the strength of the wall of Burrinjuck Dam and the water level was lowered while remedial work was carried out.

With reduced generating ability there, the Canberra Power Station and others in southern NSW, such as Yanco, generated at full capacity. Also two 1,500 kW Brush-Ljungstrom turbo generators which had been taken out of Port Kembla Power Station were installed at the Canberra Power Station, together with two and Wilcox boilers of 20,000 lb/hour (9,100 Kg) capacity at 200 lb per square inch (1,400 kPa) and 600 F (316 C) Superheat. These were commissioned and on the line on 28 February, 1939. The total generation from Canberra paralleled with the NSW Grid was 5,100 kW. In late 1938, a second 66,000 volt line from Goulburn was connected to the Canberra Switchyard, thus connecting Burrinjuck and Port Kembla Power Stations.

This was later strengthened by a 132 kV line paralleling it between Goulburn and Burrinjuck.

The steam plant at Kingston ran in this fashion generating up to 5,000 kW, regularly at first and later sporadically as required until early 1942 when it was no longer required for grid purposes as Burrinjuck with doubled capacity was then available.

The original 5.5 kV switchboard
Fig. 6.5: The original 5.5 kV switchboard at Kingston. Photo: ACTEA.

From May 1942 the BTH 1,500 kW turbo alternator ran 20 hours per day separately from all other load, to supply the swinging load of a very large transmitter at Belconnen Naval Station at the very close voltage regulation required and did so until after the war. This was considered necessary as spare valves were limited and unobtainable during the war and the Navy did not wish to subject them to the fluctuations due to lightning transients on a grid system traversing the whole of New South Wales.

All power station plant was again pressed into use in 1948 due to the general shortage of generating plant in New South Wales, combined with the rapidly increasing demand for electricity. It ran regularly until 1955 and sporadically until 1957 when it was closed down. Prior to this, in 1947, one Bellis and Morcom generator was sold and installed at the Mount Burr Forestry Mills, South Australia where it produced both electricity and exhaust steam for the timber drying kilns.

The two Bellis and Morcom engines
Fig. 6.6: The two Bellis and Morcom engines driving Brush alternators before the BTH alternator was installed. Photo: ACTEA.
The British Thomson Houston Turbo alternator
Fig. 6.7: The British Thomson Houston Turbo alternator. Photo: ACTEA.

All existing machinery was sold for scrap in 1965 but the building which is a mass of concrete still remains near Wentworth Avenue, Kingston where it is used by the Electricity Authority for a variety of purposes.

Lightning arrestors
Fig. 6.8: Lightning arrestors being installed at Kingston sub-station in 1928. Photo: ACTEA.

Diesel Power Station, Kingston

About 1950, the Electricity Commission of NSW, which was suffering a shortage of generating plant and transmission capacity to serve New South Wales requirements, installed a number of “packet” stations, both steam and diesel, throughout New South Wales and as part of this project in 1953, installed a diesel generating station at Kingston which comprised four Harland and Wolfe diesel engines direct coupled to Brush generators each of 1,250 kVA capacity generating at 3,300 volts. This was stepped up to 11,000 volts and connected to the temporary 11,000 volt busbars at the Kingston substation.

This station, which as well as the steam power station, generated from 1953 to 1956, was sold to the Commonwealth in 1960 and remains there to be used as a standby in the case of total shut down. There are only three diesel alternators left, so the capacity of 3.5 MW compared with Canberra’s peak load of about 500 MW, could only be used for very minor essential loads.

Bulk Supply and Zone Substations

Prior to 1 September, 1929, when it was put into service, the Public Works Department of NSW designed and constructed a bulk substation at Kingston to receive, control and step down the supply of 66,000 volts from Burrinjuck.

The substation comprised two banks each with three single phase transformers to Berry (British Electric Transformer Co.) manufacture of 600 kVA capacity each and had a ratio of 66,000/6,600 volts.

The output from each regulator was fed through a Berry 1,800 kVA Auto transformer star connected 6,600/5,500 volts ratio, thence through two GE (America) Autoreclosing OCB’s in the Power House basement with a metering panel to the Federal Capital Commission’s duplicate 5,500 volt open busbar in the engine room, from which the local 5,500 volt feeders emanated.

On the 66,000 volt side the transformer banks were protected by very long liquid fuses mounted on the steelwork of the sub-station. These were replaced by two Metro-Vick bulk oil three phase circuit breakers.

As an indication of the size of the undertaking at that time, the maximum demand of the Canberra load dropped from 1,200 kVA to 1,174 kVA for 1930-31 but was still the largest load on the Southern NSW system.

In late 1938 a 66,000 volt line from Goulburn tied in with the Burrinjuck line at Canberra Substation thus connecting Burrinjuck generating station with that of Port Kembla. In 1938 also, BTH type JB429 bulk oil circuit breakers were fitted to the terminations of the 66,000 volt lines from Burrinjuck and Goulburn. Later, at the end of 1938, a third circuit breaker of the same type was fitted to an outgoing 66,000 volt overhead line which fed Captains Flat.

A seven panel 11 kV Westinghouse truck switchboard was installed in a brick building at the eastern end of the Kingston Substation in 1938 and was gradually connected to the 6.6 kV system until it comprised the following panels:

Brush-Ljungstrom Generators 5 and 6
Transformer Secondaries No. 1 and No. 2
Canberra Load (to Auto Transformers) No. 1 and No. 2
Canberra Load No. 3 (to Cotter Line Auto Transformers)

The bulk metering was then transferred from the 5,500 volt busbars to the 6,600 volt busbars.

In November 1940 the No. I bank of 3 x 600 kVA single phase 66/6.6 kV transformers was replaced by a Crompton Parkinson Tap Changing Transformer 5,000 kVA capacity 66/6.6 kV ratio.

In 1946, the remaining bank of single phase transformers (No. 2) was replaced by an AGE tap changing transformer of 7,500 kVA capacity.

These remained in service until 14 October 1953 when both the main 66,000/6,600 volt tap changing transformers were replaced by two English Electric 10 MVA 66/11 kV tap changing transformers and our supply voltage changed toll kV from 6.6kV.

With the demand for electricity increasing at a very high rate, the Electricity Commission of New South Wales built a large substation in 1957 at Oaks Estate near Queanbeyan to cater for Canberra, Queanbeyan and Captains Flat. It was of 120 MVA capacity and 132/66 kV ratio, reducing the voltage from the 132 kV lines from Yass and Cooma.

In 1957 one of the 10 MVA Main Transformers at Kingston was removed and two 15 MVA English Electric 66/11 kV were installed, ASEAP Small Oil Content Circuit Breakers controlling the primary side of the new transformers. The Electricity Commission of NSW also changed the incoming BTH 66 kV Incoming Circuit Breakers with ASEA, Circuit Breakers of higher fault capacity. These were changed in 1956, 1957 and 1961.

In the early fifties, Canberra engineers saw the necessity for a number of zone sub-stations and decided to build a 66 kV ring which involved taking supply at Oaks Estate Substation at 66 kV, running initially two lines from there to Kingston Substation which Canberra Electric Supply had bought from the Electricity Commission of NSW. The lines were constructed and put in service in May, 1959.

In 1959, Canberra Electricity Supply took over the Kingston Substation and in 1961 replaced the remaining 10 MVA Main Transformer with a 15 MVA Transformer of Tyree Manufacture. In the same year the first of the new Zone Substations at North Ainslie was built and commissioned in May, 1961.

An 11 kV switchroom at the western end of the Kingston switchyard had been built since 1948 but the 11 kV switch- gear was not designed and installed until 1960. At that time a gradual changeover of 11 kV feeders occurred until the outdoor 11 kV busbar and its plethora of cubicle circuit breakers were eliminated. The switchroom was extended to accommodate additional 11 kV switchgear and the switchboard now comprises 32 panels.

In 1965 a fourth 15 MVA transformer of Tyree Manufacture was added and all transformers were fan cooled, giving a total capacity of 74 MVA with 24-11 kV feeders emanating from it.

A fifth transformer of 19 MVA capacity was moved in from North Ainslie Substation in 1974 and remains as a standby for the other four.

North Ainslie 66 kV Zone Substation

This substation was built on land at the corner of Majura Avenue and Officer Crescent, Ainslie. The first stage was completed and commissioned in May 1961 and comprised 2-15 MVA Tyree tap changing transformers of ratio 66/11 kV.

On the 11 kV side there was an open busbar with a centre tie circuit breaker feeding to a cubicle type outdoor switchboard of E.C.N.S.W. pattern manufactured by Standard Waygood and comprising 13 panels.

To feed this substation a 66 kV overhead line was constructed from Kingston Substation to North Ainslie Substation using the original (1929) double circuit Burrinjuck and Goulburn poles across the river flats to the rear of Mt Ainslie and thence new construction. A further 66 kV line was built from North Ainslie Substation along Phillip Avenue to join the original Burrinjuck Line behind Crace Hill.

In 1962 the 66 kV overhead line ring was completed from Crace Hill behind Black Mountain through Woden and back to the EC NSW Substation at Oaks Estate. The line conductor was steel cored aluminium of 0.2 inch copper equivalent with one conductor per phase and totalled about 32 circuit miles in length.

In 1963 an additional 15 MVA Tyree tap changing 66/11 kV transformer was connected and in 1965 fan cooling was fitted to all transformers giving a total capacity of 57 MVA.

66 kV Woden Zone Substation

The Woden Zone Substation was located near the corner of Devonport and Heyson Street, Lyons and was commissioned in 1964 with two Tyree 15 MVA tap changing transformers which were fan cooled in 1965 giving a total capacity of 38 MVA. A control building on the site housed an 11 kV Westinghouse Switchboard with 17 feeders.

132 kV double circuit transmission tower
Fig. 6.9: 132 kV double circuit transmission tower. Photo: ACTEA.
132 kV double circuit terminal tower
Fig. 6.10: 132 kV double circuit terminal tower. Photo: ACTEA.

Change of Sub Transmission Voltage from 66 kV to 132kv

Despite all the above work which was carried out to maintain supply and keep up with the demands for electricity, it was evident that the rate of increase of demand, always much higher than that. of population, would require drastic action to cope with projected future requirements so in the early sixties, consultation with the Electricity Commission of New South Wales resulted in the decision to built a 330/132 kV Substation at Weetangera district, now Charnwood. This substation would have an initial capacity of 750 MVA and a final capacity of 1,500 MVA occupying a land area of 69 acres (28 ha). Canberra would then take bulk supply from them at this centre at 132 kV, retaining the 66 kV bulk supply point at Oaks Estate, until all Canberra load could be transferred to the 132 kV bulk supply point.

The ACT Electricity Authority commenced design of a 132 kV system with some novel features. To preserve the amenity by using a minimum number of 132 kV lines, it was decided to use tower lines of pleasing proportion and the highest capacity practicable. They were 2-0.5 square inch (322 mm2) copper equivalent SCA (Moose) conductors per phase, each line capable of transmitting 500 MVA.

Every care was taken in close consultation with officers of the National Capital Development Commission to reduce the visual impact of the 132 kV lines as much as possible, and to coordinate their location with the general planning as known at that time. Even tower design was chosen to present a pleasing aspect.

Two lines were built in 1967, emanating from the Electricity Commission of NSW 330 kV substation, one along the Molonglo River Valley to Woden and one through the as yet unbuilt Belconnen Valley to a substation at the foot of Black Mountain and thence to Woden, a total route distance of 26 miles (42 km).

132 kv Circuit Breaker
Fig. 6.11: 132 kV Circuit Breaker.
132/11 kV Transfonner
Fig. 6.12: 132/11 kV Transformer.

Main Zone Substations 132/11 kV

Having decided to take supply at 132 kV which was then the highest sub-transmission voltage used in Australia, a further step, unprecedented at that time in Australia, of direct transformation from 132 kV to 11 kV was adopted. These substations were to be of 60 MVA firm capacity with space available for the future addition of another transformer to enable an increase to 120 MVA later if required. However, the inherent fault capacity available required refined relay protection treatment to prevent widespread damage on fault; and with this done the system as designed and constructed has proved successful in service.

With the first substation installed adjacent to residential areas, the operation of 132 kV air blast circuit breakers with their attendant noise was considered undesirable so small oil volume hydraulically operated circuit breakers (Oerlikon, Switzerland) of 2,000 ampere rating and 8,000 MVA rupturing capacity were installed.

The tap changing transformers were of Tyree manufacture with an ON rating of 30 MVA, an OFB rating of 45 MVA and with each capable of handling a winter peak load of 60 MVA at the Canberra load cycle. They have 18% impedance on 30 MVA to keep the fault value at the 11 kV busbars at a level suitable for the existing 11 kV switchgear on the system.

The transformer connections were ydl and an earthing transformer was used on the 11 kV side which limited the earth fault to 3,000 amperes.

This means simply, that the transformer design was such that each had a capacity of 30 MVA with natural cooling, 45 MVA with forced oil and air cooling, but 60 MVA at the Canberra load cycle in winter when the load peaks. Thus if one transformer was switched out on fault in the winter, the other transformer could carry the whole 60 MVA load.

The transformers are operated each with its own 11 kV feeder load but with a “flip-flop” arrangement so that one transformer automatically takes over the other one’s load should it trip out on fault.

The high current on the 11 kV side of the transformers under emergency conditions required two Main Transformer OCB’s per transformer as 11 kV OCB’s with capacity exceeding 2,000 amperes were unusual. The 11 kV switchboard was of Brush manufacture with 500 MVA rupture rating double busbar and with 16 outgoing feeder circuit breakers each of 800 ampere capacity.

City Zone Substation 132/11 kV

This was situated on land occupied by a former Caravan Park at the foot of Black Mountain and is not only hidden from sight but was given architectural treatment to merge it with the environment as far as possible. It was put into service in July 1967.

Woden Zone Substation 132/11 kV

The existing 66 kV/11 kV zone substation at Woden was converted to 132 kV operation in two stages, the first transformer being put in service in July 1967 and the second in February 1968 when the 66/11 kV transformers and switchgear were removed.

Latham Zone Substation 132/11 kV

This substation situated near Rudall Street, Latham, was constructed in line with the standard adopted for City Zone Substation and went into service in March, 1971, to supply the growing load in the Belconnen Valley. This was the first substation constructed in that area and connected in to a 132 kV line which had been erected prior to any development in the valley. In 1982 a third 60 MVA transformer was installed making the firm capacity of the substation 120 MVA.

Mains plan of the city in 1918
Fig. 6.13: Mains plans of the city in 1918.

Wanniassa Zone Substation 132/11 kV

This 60 MVA zone substation was constructed adjacent to Athllon Drive, Wanniassa and fully put in service during April, 1975. It was fed from two 132 kV feeders supported on wood poles and emanating from the Woden Zone Substation. In 1981, a third 60 MVA transformer was installed making the firm capacity of the substation 120 MVA.

Belconnen Zone Substation 132/11 kV

This 60 MVA zone substation adjacent to the Belconnen Town Centre was commissioned in April 1977, connected into the same 132 kV feeder as Latham Zone Substation and feeds the surrounding residential areas as well as the Belconnen Town Centre.

This substation saw the first installation in the Territory of the new type of sulphur hexafluoride gas circuit breaker, a type of circuit breaker fairly new to Australia but with many advantages.

Mains plan of the metropolitan area 1982
Fig. 6.14: Mains plan of the metropolitan area 1982.

City East Zone Substation

In the middle seventies it was evident that action should be taken to diminish and phase out our demand for bulk electricity from the 66 kV bulk supply point at Oaks Estate1 near Queanbeyan. With this in view, and to cope with the ever increasing load demands, a switching station was established at Bruce allowing two 132 kV lines each of 260 MVA capacity to be connected through circuit breakers and run to a new zone substation at the foot of Mount Ainslie. This substation would then be available to take new load in the area and to take over the 11 kV supply from the Ainslie 66/11 kV substation.

The substation of 60 MVA firm capacity was commissioned in August 1979 and commenced taking over load from the Ainslie 66/11 kV substation. With this 132 kV substation in service only the original Kingston substation requires changing from 66 kV to 132 kV supply and this changeover, together with resiting near the Causeway, is now in hand.

The maximum demand at the 1982 winter peak was 485 MW and this was fed from both systems with 431 MW from 132 kV supply and 54 MW from 66 kV supply.

Distribution System

The original distribution voltage at 1915 was the same as the generated voltage, namely 5,000 volts later increased to 5,500 volts with step up transformers at Kingston delivering electricity at 11,000 volts to the Cotter Pumping Station with a later tee off to Mount Stromlo (1922). In fact the 11,000 volt line from Kingston to the Cotter was erected in 1914 and was one of the first lines of that voltage in Australia and the first to use all aluminium wire. The feeders emanated from Kingston Substation and were all overhead except for underground cable in the Parliamentary area.

From 1946 onward a programme was put in hand not only to increase all feeders to 11 kV operation but to underground a considerable length of them. With shortages of capacity and materials this took a long time but on 14 October 1953, bulk supply was taken at 11 kV and all feeders except some undergrounded feeders in the Parliamentary area which operated through auto transformers at 5,500 volts, were converted and operating at 11 kV. The cable was replaced in the Parliamentary area shortly afterward and since then all feeders are operated at 11 kV excepting two 22 kV feeders- one to the Cotter Pumping Station and the Upper Cotter, and one to Tidbinbilla.

With the change to 11,000 volt distribution considerable underground cable was used, with the result to date that 11,000 volt lines are run in less than one third of the streets and nearly one half of them are underground in the City area. As the rate of increase of demand becomes known in each district and funds are available, it is envisaged that they will all be underground before very long, leaving the streets as uncluttered tree-lined avenues as visualised by Walter Burley Griffin.

To the year 1981-82, there were 1,410 route kilometres of distributor in the City area of which 640 kilometres is underground.

Distribution Substations 11,000 Volts to 415/240 Volts

Apart from a few substations in buildings, mainly Parliament House (which also fed East and West Blocks by low voltage cable) and the Cotter Pumping Station, all early distribution substations were of the two pole overhead type.

As the City developed, it was necessary to research all known systems of distribution networks from the viewpoint of economics and operating efficiency, especially for ease of restoration of supply after fault. It was decided to use an open ring system with two 11,000 volt feeds to each substation in the City area and that this system would be the best until motor traffic problems restricted operator movement. Special arrangements for immediate alternate supply were made where this was absolutely essential.

The substations are now a mixture of overhead, one and two pole to 500 kVA, indoor, unlimited capacity, ironclad kiosk to 750 kVA capacity and pad mounted transformers to 750 kVA capacity each used to their best advantage. The total number of substations in service at 30 June 1982 were:—

Indoor Substations 150
Kiosk Substations 202
Pad Mounted Transformers 1048
Overhead Pole Substations 1479
Ground Type Substations 1479
Total 2893

Low Voltage Mains 415/240 Volts

Underground cable is used extensively in commercial areas and also for feeders into the domestic reticulation system but rear of lot overhead mains with underground or overhead services to the houses are used in domestic areas. This was used from the outset and was initiated by Walter Burley Griffin. Experience has shown that there are few of the problems of easement and access that are encountered in other places, due to Canberra’s system of leasehold tenure of land.

This mains system provides for ease of augmentation and this is essential in Canberra when it is considered that in 1982 it had an average annual usage of 11,258 kWh compared with an Australian average of 6,062 kWh per domestic customer.

The overhead lines are in general mounted on 9.2m wood poles (originally 7.6m) with 1.75m crossarms, the conductors being of copper until recent years and then of aluminium and the standard crossection is 65mm2 copper or its equivalent in aluminium.

Typical pad mounted sub-station 11 kV/415V
Fig. 6.15: Typical pad mounted sub-station 11 kV/415V.

Progress of Electricity Supply in the ACT

At the turn of the century with both Canberra and public Electricity Supply in their infancies, it was decided that electricity with its unpollutive characteristic especially with hydro-electric generation would be the most suitable energy source for the garden City to come. This decision was taken when nearly all the cities of the world relied on coal gas for its distributed energy.

The growth in usage of electricity in the ACT has been tremendous by any standard and far higher than the growth in population. An indication of this growth is given by the following table:

Year Population Maximum Demand MW Units bought MkWh
1928-1929 6,880 1.04 4.9 (est)
1938-1939 10,800 2.40 12.28
1948-1949 19,639 6.44 30.50
1958-1959 46,072 25.32 103.60
1968-1969 121,662 118.30 459.70
1978-1979 220,000 359.30 1,386.00
1981-1982 230,000 485.00 1,602.00

(Population figures prior to 1959 are for urban areas only. Electricity was subsequently extended to rural areas and the figures for 1959 and later include the whole of the ACT. Queanbeyan, fed from Kingston power house from 1920 to 1939, is not included in the population figures.)

In 1981 the ACT accounted for only 6 per cent of the total demand of 8,011 megawatts on the NSW electricity grid. Half of the ACT’s consumption was domestic.

Organisational Responsibility

For many years responsibility for the supply of electricity in Canberra passed from department to department and for most of this time it was carried out in conjunction with all other electrical work such as contracting, day labour and maintenance required by the Commonwealth in the ACT. In fact, even today, a considerable amount of recoverable work, especially maintenance in buildings and undertakings, is still being done by the ACT Electricity Authority.

The movement of responsibility between departments was not as disruptive as it appears as in most cases the work was conducted by the same staff.

All persons in charge of the undertaking have been corporate members of The Institution of Engineers, Australia from its inception and the number of corporate members employed has varied from two to 20.

The following list shows the departments and authorities that have been responsible for electricity supply in the ACT:—

Department of Home Affairs — (Works cell)
(1/1/01—11/11/16); Department of Works and Railways
(14/11/16-1/1/25); Federal Capital Commission
(1/1/25-30/4/30); Department of Works and Railways
(1/5/30-12/4/32); Department of the Interior
(13/4/32-23/11/38); Department of Works — (engineering)
(24/11/38-26/4/39); Department of the Interior
(27/4/39-2/2/45); Department of Works — (engineering)
(2/2/45-13/7/45); Department of Works and Housing
(13/7/45-12/10/53); Department of the Interior(13/10/53-30/6/63); ACT Electricity Authority
(1/7/63—)

Officers in charge

There have been six officers in actual charge of operations since 1914, all of whom have been corporate members of The Institution of Engineers, Australia at one time or another. The dates are as close as can be obtained:

H.P. Moss (visited from Melbourne) (1914-1925);
S.W. Cook (1925-1927);
AM. Fraser (1927-1944);
W.E. Gray (1944-1952);
H.A. Jones (1952-1975);
WE. Bolton (1975- ).

The ACT Electricity Authority was formed under the ACT Electricity Supply Act No. 72 of 1962 which came into force on 1 July 1963. The first meeting of the Authority was held in the conference room at Civic North Offices on 2 July 1963 when the chairman was delegated to carry on with the day to day management of the undertaking.

The Authority was managed by a full time chairman who was assisted on a part time basis by a representative of the Department administering the Territory and an elected representative of the local Advisory Council, later House of Assembly.

Since 1963, the two full time chairmen have been H.A. Jones (1/7/63-21/1/75) and W.E. Bolton (1975 to date).

Elected representatives of the local government body (no executive functions) have been: J.H. Pead (1/7/63-17/ 10/67); R.R. O’Keeffe (17/10/67-12/10/70); J.H. Pead (13/10/70-31/10/74); R.P. Vallee (1/11/74-4/7/79); P.R. Whalan (5/7/79-30/6/82) and P.R. Kobold (1/7/82 to date). They have one vote in three on the Authority to decide any business.

The three appointed representatives of the Department since 1963 have been W. McGregor (1/7/63-8/5/70); J.H. Marshall (9/5/70-1/10/74); and WE. Lawrence (2/10/74- ).

Buildings, offices and depots

Shortly after the ACT Electricity Authority was formed in 1963 it was given permissive occupancy of Block I Section 8 Kingston, an area comprising about 5.46 ha and fronting Wentworth Avenue. On this land, was the old power station (1915), the Kingston zone substation (1929) and its 11 Kv switch room (1948), the linesman’s depot (1958) and the electrical workshop (1956 extended 1967).

The area originally contained not only the power station and the adjacent mechanical fitters shop but a temporary building which initially contained the first joiners shop and other trades, then became the electrical workshop until it was dismantled in 1974. In that year a new stores building was erected on the site and amalgamated with the old fitters shop. The site also contained the first transport depot and fire station, some buildings of which still remain, and three houses by the river now demolished.

As the City grew, it was necessary to decentralise maintenance and construction depots and a first building on the corner of Wakefield Avenue and Limestone Avenue, Ainslie was completed on 8 January 1973.

Electricity House
Fig. 6.16: Electricity House, 1982.

Originally the Electric Supply offices were incorporated in the Acton offices which were demolished to make room for extensions to the Royal Canberra Hospital. When the Federal Capital Commission terminated on 30 April, 1930 the engineering and consumer’s side were transferred to the Jolimont Offices of the Department of Works and Railways in Alinga Street, City.

The Department of Works was incorporated in the new Department of the Interior on 13 April 1932 and moved shortly afterward back to Acton offices. Electric supply engineering moved from there to No. 2 Unit, Barton with the Department of Works and Housing. The Consumer’s records were moved at that time to Jolimont Offices.

On 13 October 1953 the Electric Supply function was re-united in the Department of the Interior at Acton Offices.

On 6 July 1957 the Canberra Electric Supply Branch moved to the Melbourne Building, West Row, Canberra City, into premises rebuilt after a fire which destroyed the Canberra University College Library. The Branch expanded into the top floor of Block 20 Section 1 City and later into Block 3, Section 3 of Hobart Place.

The growth of the function and lack of availability of office space decided the ACT Electricity Authority to obtain a Crown Lease of Block 1 Section 12 City and to build Electricity House, combining offices, a large distribution substation and a distribution control centre.

The tender of $2,701,658 of Civil and Civic Pty Ltd was accepted for the construction of Electricity House on 30 May 1967 to plans and specifications produced by Peddle Thorpe and Walker Architects. Rankine and Hill were the engineering consultants and Rider, Hunt and Partners were the quantity surveyors.

The building was completed at slightly less than the tender price and occupied on 20 January, 1969.

The building has a gross floor area of 11,220m2 and should be large enough for a headquarters building for the foreseeable future. For customer convenience a small office with demonstration theatre was opened in Woden Plaza on 19 September, 1972, and a small office was opened in Belconnen Mall on 22 August, 1978.

Electricity supply in Canberra has now reached a size never contemplated originally, with a maximum demand approaching 500 Megawatts and a total annual revenue of $56.0 million and rising. It is a large organisations by any standard.

It is now run completely on behalf of its customers with staff paid by its customers and is sensitive to its customer’s requirements.

The technical equipment and the accommodation accords with the best modern practice and the outlook of those guiding its destiny is progressive.

Attracted by the high price of oil, reticulated gas is now making its appearance in the City and although it will compete mainly with fuel oil, it will also have some effect in moderating the demand for electricity in heating homes in the winter.

With all sources of energy being used as a taxing medium the economic pendulum will swing back and forth but, no matter what happens, electricity will continue to be the major source of energy for Canberra and its life blood.